GATE EE · Power Systems
Generate GATE-level questions on Protection systems. Focus on: 1. Relays: Overcurrent, Directional, Distance (Mho/Reactance), and Differential protection. 2. Circuit Breakers: Arc interruption theory, Restriking voltage, and RRRV. 3. Protection of Generators, Transformers, and Transmission lines.
25 questions · 20 PYQs · 0 AI practice · GATE EE 2027
🎯 These are sample questions
Just sign in to unlock everything. Free for all students.
The figure shows the single line diagram of a 4-bus power network, Branches , and have impedances and per-unit (pu), respectively, where , with and . The current drawn from each load bus (marked as arrows) is equal to pu, where . If the network is to operate with minimum loss, the branch that should be opened is

For the three-bus power system shown in the figure, the trip signals to the circuit breakers to are provided by overcurrent relays to , respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus and the loads with isolation of minimum portion of the network using minimum number of directional relays is

A balanced delta connected load consisting of the series connection of one resistor and a capacitor in each phase is connected to three-phase, supply terminals through a line having an inductance of per phase, as shown in the figure. Considering the change in the supply terminal voltage with loading to be negligible, the magnitude of the voltage across the terminals in Volts is ____ (Round off to the nearest integer).

The most commonly used relay, for the protection of an alternator against loss of excitation, is
In a 132 kV system, the series inductance up to the point of circuit breaker locationis 50 mH. The shunt capacitanceat the circuit breaker terminal is 0.05 . The critical value of resistance in ohms required to be connected across the circuit breaker contacts which will give no transient oscillation is_____
The total impedance of the secondary winding, leads, and burden of a 5 A CT is 0.01 . If the fault current is 20 times the rated primary current of the CT, the VA output of the CT is ________
A power system with two generators is shown in the figure below. The system (generators, buses and transmission lines) is protected by six overcurrent relays . Assuming a mix of directional and nondirectional relays at appropriate locations, the remote backup relays for are
A 3-phase transformer rated for 33 kV/11 kV is connected in delta/star as shown in figure. The current transformers (CTs) on low and high voltage sides have a ratio of 500/5. Find the currents , if the fault current is 300 A as shown in figure.
The over current relays for the line protection and loads connected at the buses are shown in the figure. The relays are IDMT in nature having the characteristic The maximum and minimum fault currents at bus B are 2000 A and 500 A respectively. Assuming the time multiplier setting and plug setting for relay to be 0.1 and 5 A respectively, the operating time of (in seconds) is_____.

A negative sequence relay is commonly used to protect
A nuclear power station of 500 MW capacity is located at 300 km away from a load center. Select the most suitable power evacuation transmission configuration among the following options

Consider a stator winding of an alternator with an internal high-resistance ground fault. The currents under the fault condition are as shown in the figure The winding is protected using a differential current scheme with current transformers of ratio 400/5 A as shown. The current through the operating coils is

A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3s. The symmetrical breaking current is
Match the items in List-I (Type of transmission line) with the items in List-II (Type of distance relay preferred) and select the correct answer using the codes given below the lists.

Voltages phasors at the two terminals of a transmission line of length 70 km have a magnitude of 1.0 per unit but are 180 degree out of phase. Assuming that the maximum load current in the line is of minimum 3-phase fault current, Which one of the following transmission line protection schemes will not pick up for this condition ?
A two machine power system is shown below. The Transmission line XY has positive sequence impedance of and zero sequence impedance of An 'a' phase to ground fault with zero fault impedance occurs at the centre of the transmission line. Bus voltage at X and line current from X to F for the phase 'a', are given by Volts and amperes, respectively. Then, the impedance measured by the ground distance relay located at the terminal X of line XY will be given by

Consider the transformer connections in a part of a power system shown in the figure. The nature of transformer connections and phase shifts are indicated for all but one transformer. Which of the following connections, and the corresponding phase shift , should be used for the transformer between A and B ?

Consider the protection system shown in the figure below. The circuit breakers numbered from 1 to 7 are of identical type. A single line to ground fault with zero fault impedance occurs at the midpoint of the line (at point F), but circuit breaker 4 fails to operate ("Stuck breaker"). If the relays are coordinated correctly, a valid sequence of circuit breaker operation is

Keeping in view the cost and overall effectiveness, the following circuit breaker is best suited for capacitor bank switching
In a biased differential relay the bias is defined as a ratio of
Want unlimited AI-generated Switch Gear And Protection questions?
Sign up free and practice with adaptive difficulty — Easy, Medium, Hard. New questions every session.
Start practising for free →