📖 Explanation
Let's define: Unit 1 outputs: At 10,000 Rs./MWh → P1=50 MW At 10,600 Rs./MWh → P1=80 MW Unit 2 outputs: At 10,000 Rs./MWh → P2=80 MW At 10,600 Rs./MWh → P2=92 MW We are to find outputs at 11,800 Rs./MWh using extrapolation for both units (assuming linearity of power vs incremental cost curve). Step 1: Find slope of output with respect to cost for each unit Unit 1 slope: 10,600−10,00080−50=60030=0.05 MW per Rs./MWh Unit 2 slope: 10,600−10,00092−80=60012=0.02 MW per Rs./MWh Step 2: Extrapolate to 11,800 Rs./MWh Cost increase: 11,800−10,600=1,200 Rs./MWh Unit 1 output: P1=80+(0.05)(1200)=80+60=140 MW (but Unit 1 is rated for 100 MW max \Rightarrow limit to 100 MW) Unit 2 output: P2=92+(0.02)(1200)=92+24=116 MW (but Unit 2 is rated for 150 MW \Rightarrow no limit hit) Step 3: Total Output Ptotal=100+116=216 MW Final Answer: 216